1 Sash with handle bar
2 Worktop
3 FAZ or AC control panel
4 Removable fascia panel
5 Extract air spigot integrated in
fume- scrubber (optional)
6 Baffle
7 H-frame with push-in underbench
unit with support and service panels
|
|
Intended use
- Protective device for the user, tested in acc. with DIN EN 14175-7:2012
- Suitable for open, thermal processes of breaking down chemicals with aggressive media such as, e.g., sulphuric acid, hydrochloric acid or aqua regia
- The construction of the fume cupboard and the materials of the inner lining of the internal workspace determine which aggressive media the device can be used for
- Extraction of fumes and aerosols from the internal workspace to prevent dangerous amounts of pollutants from escaping into the laboratory
- To prevent the formation of dangerous potentially explosive atmospheres in the internal workspace
- Protection from splashes of hazardous substances in the internal workspace
- Protection from Ḁying particles, bodies or parts from the internal workspace
- Fume cupboards constructed in acc. with DIN EN 14175-7:2012 not permitted for use with radioactive substances or microorganisms
- For working with high thermal loads in connection with acid digestions in the internal workspace (heat sources of 4 KW per metre of clear width in the fume cupboard)
|